FX series Mitsubishi plc error list (61-65)
Error number (D806*): 0000
Error message: NO ERROR--No error occurred. Error content and cause: No error occurred. Countermeasure: Check if the connection between the host and the I/O expansion base/module is normal.
Error Number (D8061) : 6101
Error message: PLC HARDWARE ERROR (PLC hardware failure)
Abnormal content: PLC stop operation error content and cause: RAM error countermeasure: Please check whether the connection between the host and the I/O expansion base/module is normal.
Error number (D8061): 6102
Error message: PLC HARDWARE ERROR (PLC hardware failure)
Abnormal content: PLC stop operation abnormal Cause: Loop error countermeasure: Please check whether the connection between the host and the I/O expansion base/module is normal.
Error number (D8061): 6103
Error message: PLC HARDWARE ERROR (PLC hardware failure)
Abnormal content: PLC stop operation error content and cause: I/O Bus error, must drive M8069=ON first. Effective countermeasures: Please check whether the connection between the host and I/O expansion base/module is normal.
Error Number (D8061): 6104
Error message: PLC HARDWARE ERROR (PLC hardware failure)
Abnormal content: PLC stop operation abnormal Cause: I/O expansion base 24V abnormal, must drive M8069=ON first. Effective countermeasures: Please check whether the connection between the host and the I/O expansion base/module is normal.
Error number (D8061): 6105
Error message: PLC HARDWARE ERROR (PLC hardware failure)
Abnormal content: PLC stopped abnormality Cause: Watchdog timer error countermeasure: Please check whether the connection between the host and the I/O expansion base/module is normal.
Error Number (D8062): 6201
Error message: PLC/PP COMMUNICATION ERROR (PLC/writer communication error)
Error content: Parity/Frame Error
Countermeasures: Please check if the connection between the host and the 20P or PC is normal.
Error Number (D8062): 6202
Error message: PLC/PP COMMUNICATION ERROR (PLC/writer communication error)
Error content: Communication error: Please check if the connection between the host and the 20P or PC is normal.
Error Number (D8062): 6203
Error message: PLC/PP COMMUNICATION ERROR (PLC/writer communication error)
Error content: Communication data summary check inconsistent countermeasures: Please check whether the connection between the host and the 20P or PC is normal.
Error Number (D8062): 6204
Error message: PLC/PP COMMUNICATION ERROR (PLC/writer communication error)
Error content: Communication string exception countermeasure: Please check if the connection between the host and the 20P or PC is normal.
Error number (D8062): 6205
Error message: PLC/PP COMMUNICATION ERROR (PLC/writer communication error)
Error content: Communication command error countermeasure: Please check if the connection between the host and the 20P or PC is normal.
Error Number (D8063): 6301
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Parity/Frame Error
Countermeasure: Whether the power of the two PLCs is on, and whether the connection between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6302
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Communication word exception countermeasure: Whether the power of the two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6303
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Incompatibility check of communication data summary check: Whether the power of two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6304
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Communication string exception countermeasure: Whether the power of the two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error number (D8063): 6305
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Communication command error countermeasure: Whether the power of the two PLCs is turned on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6306
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Over the monitoring time countermeasure: Whether the power of the two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6312
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Parallel operation error countermeasure: Whether the power of the two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6313
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Parallel operation total inspection check inconsistent countermeasures: Whether the power of the two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8063): 6314
Error message: PARALLEL LINK ERROR (parallel operation communication error)
Error content: Parallel operation string error countermeasure: Whether the power of the two PLCs is on, and whether the connection line between the host and the parallel operation module is correctly connected.
Error Number (D8064): 6401
Error message: PARAMETER ERROR (parameter error)
Error content: Program summary check inconsistent countermeasures: Turn the PLC to STOP and check if the parameter settings are correct.
Error Number (D8064): 6402
Error message: PARAMETER ERROR (parameter error)
Error: The memory capacity setting is incorrect. Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.
Error Number (D8064): 6403
Error message: PARAMETER ERROR (parameter error)
Error content: The power failure holding area setting is incorrect. Countermeasure: Turn the PLC to STOP and check if the parameter setting is correct.
Error Number (D8064): 6404
Error message: PARAMETER ERROR (parameter error)
Error content: The annotation area setting is incorrect. Countermeasure: Turn the PLC to STOP and check if the parameter setting is correct.
Error Number (D8064): 6405
Error message: PARAMETER ERROR (parameter error)
Error content: The file buffer area setting is incorrect. Countermeasure: Turn the PLC to STOP and check if the parameter setting is correct.
Error number (D8064): 6409
Error message: PARAMETER ERROR (parameter error)
Error content: Other settings are incorrect. Countermeasure: Turn the PLC to STOP and check if the parameter settings are correct.
Error Number (D8065): 6501
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: The combination of instruction and operand is incorrect. Countermeasure: Please check if each instruction in the program is used correctly.
Error number (D8065): 6502
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: There is no OUT T before the set value, OUT C command countermeasure: Please check whether the usage of each instruction in the program is correct.
Error Number (D8065): 6503
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: OUT T, there is no set value after OUT C, and the number of operands of the application instruction is insufficient. Countermeasure: Please check whether the usage of each instruction in the program is correct.
Error Number (D8065): 6504
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: Repeat the use of the number of P, interrupt the insertion of the input number and repeat the use of the high-speed counter input number. Countermeasure: Please check whether the usage of each instruction in the program is correct.
Error number (D8065): 6505
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: The specified component is out of range. Countermeasure: Please check if each instruction in the program is used correctly.
Error Number (D8065): 6506
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: Use undefined instruction countermeasures: Please check if each instruction in the program is used correctly.
Error Number (D8065): 6507
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: P number error countermeasure: Please check whether the usage of each instruction in the program is correct.
Error number (D8065): 6508
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: I number error countermeasure: Please check whether the usage of each instruction in the program is correct.
Error Number (D8065): 6509
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: Other countermeasures: Please check if each instruction in the program is used correctly.
Error Number (D8065): 6510
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content: Improper use of the N number of the MC/MCR: Please check if the usage of each instruction in the program is correct.
Error Number (D8065): 6511
Error message: SYNTAX ERROR (PLC stopped running, grammar error)
Error content interrupt Insertion input number and high-speed counter input number repeated use countermeasures: Please check whether the usage of each instruction in the program is correct.